North American Network Operators Group Date Prev | Date Next | Date Index | Thread Index | Author Index | Historical Re: San Francisco power outages imminent
> Actually, thats another question I am somewhat interested in.. what
> are the policies of various people on testing and excercising
> generators and other backup equipment?
We run our gensets for five minutes on line gas, and five minutes
on tank gas, each week, and test a hot cut-over (exercising the
batteries and transfer switches as well) once a month.
> How many customers ask about
> such things before locating equipment vs just asking "do you have
> backup power?"
Only once that I can recall.