Crap grounds...

  • From: blitz
  • Date: Sat Jan 11 04:40:48 2003


Yes, seen that and worse..

How about the di-electric fittings on either a water heater, or a water meter?

Of course, "no one" would use a HOT water line as a ground, but it does happen, and
I believe the NEC requires both be bypassed now with a conductor the same size as power neutral.

I routinely jump unbridged meters and water heaters (cold pipe to hot) with a #6 when in doubt.
Just to be sure.
I've got lots of #6 in the scrap box, and plenty clamps...

Cheap insurance..